Subjects: Dynamic and Electric Engineering >> Electrical Engineering submitted time 2022-10-11
Abstract: The temporary overvoltage (TOV) during fault recovery process of renewable energy system seriously restricts the development of renewable energy. However, the existing research lacks quantitative indicators of the TOV. Therefore, based on the mechanism of TOV, this paper proposes a method to quantify the TOV risk of multiple renewable energy station system (MRESS) considering the reactive power saturation characteristic. Firstly, based on the TOV mechanism of MRESS, the analysis model under different factors during fault recovery is established, and then the rationality of TOV assessment based on phasor model is demonstrated. After fully considering the saturation characteristics of converters after fault and the interaction between renewable energy generators, an evaluation method for TOV of MRESS is derived. Through analyzing the relationship between TOV of the system and short-circuit ratio, the temporary overvoltage short-circuit ratio (TOVSCR) of MRESS and its application method are proposed. Simulation results show that the proposed method can effectively evaluate the TOV risk and safety margin of the MRESS.
Peer Review Status:Awaiting Review